Current Rating For Copper & Aluminum Conductors Vulcanized Rubber, PVC or Polythene Insulated Cables (Single Twin, Three & Four Core)
Item |
Standard Copper Conductor |
|
Continuous Current Rating (Subject to Voltage Drop) (Amps) |
Standard Aluminium Conductor |
Area
(Sq. In) |
Strand
(Inch) |
In conduit troughing or casing (2 single Core Cables) |
Bunched in Free Air or Open Trench |
One
Twin
Core
DC or AC |
One 3 or 4 Core Cable Balanced 3 Phases |
Area
(Sq. mm) |
Strand
(mm) |
2 Single Core Cables |
3 or 4 Core Cables |
| 1 |
0.0015 |
1/004 |
5 |
5 |
5 |
5 |
5 |
- |
- |
| 2 |
0.002 |
3/.029 |
10 |
10 |
10/9 |
10 |
8/7 |
1.5 |
1/1.40 |
| 3 |
0.003 |
3/.036 |
15 |
15 |
13/12 |
15 |
10/11 |
2.5 |
1/1.80 |
| 4 |
0.0045 |
7/029 |
20 |
20 |
15 |
20 |
15 |
- |
- |
| 5 |
- |
- |
20 |
20 |
17 |
20 |
14 |
4 |
1/2.80 |
| 6 |
- |
- |
27 |
27 |
24 |
27 |
19 |
6 |
1/2.80 |
| 7 |
0.007 |
7/.052 |
28 |
28 |
25 |
28 |
20 |
- |
- |
| 8 |
- |
- |
34 |
34 |
31 |
34 |
24 |
10 |
1/3.55 |
| 9 |
0.01 |
7.044 |
36 |
36 |
32 |
36 |
25 |
- |
- |
| 10 |
0.0145 |
7/052 |
43 |
43 |
39/38 |
43 |
30 |
16 |
4/1.70 |
| 11 |
0.225 |
7/.64 |
53 |
53 |
48 |
53 |
37 |
- |
- |
| 12 |
- |
- |
59 |
59 |
54 |
59 |
42 |
25 |
7/2.24 |
| 13 |
.03 |
19/044 |
62 |
62 |
56 |
62 |
43 |
- |
- |
| 14 |
- |
- |
69 |
69 |
62 |
69 |
48 |
35 |
7/2.50 |
| 15 |
0.04 |
19/052 |
74 |
74 |
67 |
74 |
52 |
- |
- |
| 16 |
- |
- |
- |
91 |
82 |
91 |
62 |
50 |
7/3.00 |
| 17 |
0.06 |
19/064 |
- |
97 |
88 |
97 |
68 |
- |
- |
| 18 |
0.075 |
19/0.072 |
- |
123 |
107 |
115 |
78 |
- |
- |
| 19 |
- |
- |
- |
134 |
118 |
118 |
82 |
70 |
19/2.24 |
| 20 |
- |
- |
- |
153 |
138 |
135 |
94 |
95 |
19/2.50 |
| 21 |
0.1 |
19/083 |
- |
160 |
140 |
140 |
98 |
- |
- |
| 22 |
0.12 |
37/064 |
- |
177 |
158 |
158 |
109 |
- |
- |
| 23 |
- |
- |
- |
184 |
170 |
162 |
114 |
120 |
37/2.24 |
| 24 |
0.15 |
37/083 |
- |
205 |
185 |
180 |
126 |
- |
- |
| 25 |
- |
- |
- |
210 |
185 |
181 |
157 |
150 |
37/2.24 |
| 26 |
- |
- |
- |
246 |
216 |
209 |
146 |
185 |
37/2.4 |
| 27 |
0.2 |
37.083 |
- |
250 |
220 |
218 |
153 |
- |
- |
| 28 |
- |
- |
- |
290 |
248 |
240 |
169 |
225 |
377/2.80 |
| 29 |
25 |
37/093 |
- |
293 |
260 |
252 |
178 |
- |
- |
| 30 |
0.3 |
37/093 |
- |
335 |
295 |
284 |
199 |
- |
- |
| 31 |
- |
- |
- |
354 |
302 |
389 |
202 |
300 |
61/2.50 |
| 32 |
- |
- |
- |
425 |
360 |
342 |
240 |
- |
- |
| 33 |
- |
- |
- |
453 |
372 |
- |
- |
400 |
31/3.00 |
| 34 |
5 |
61/0.93 |
- |
480 |
410 |
- |
- |
- |
- |
| 35 |
- |
- |
- |
480 |
411 |
- |
- |
500 |
91/2.65 |
| 36 |
- |
- |
- |
565 |
484 |
- |
- |
625 |
91/2.65 |
| 37 |
75 |
91/103 |
- |
610 |
520 |
- |
- |
- |
- |
| 38 |
1.0 |
127/103 |
- |
740 |
630 |
- |
- |
- |
- |
** Rating Ambient Temperature 30oC
For Ambient Temperature other than 30oC
Rating should be multiplied by the following Rating Factors 25oC 35oC 40oC 45oC
Rating Factor 1.13 96 69 47
In the above table current ratings (subject to voltage drop) have been given for Copper conductor cables (in the new metric sizes as per I.S. 1753-1961) from this chart, the requires size of Aluminium conductor can be established if either the Current Rating or the size of the Copper Conductor is known. |
|
|
|
|
© Copy Right 2004 Shyam Net, Cochin-16, Kerala, India. All rights reserved. Revised:
August, 2005
www.hotelskerala.com | www.travelskerala.com | www.hotelschennai.com | www.hotelsbangalore.com
|